Power in Three-Phase Systems
How to calculate power, and the advantages over single-phase.
9 min read
Three-phase power calculations are straightforward if you remember the formula. It's the same concept as single-phase, just distributed across three lines.
The formula revisited
P = โ3 ร V_line ร I_line ร cos(ฯ)
Where:
- โ3 โ 1.73
- V_line is the voltage between two phase lines (400 V in UK)
- I_line is the current in each line
- cos(ฯ) is the power factor
If you measure two of these, you can find the third.
Example calculations
Example 1: A motor on 400 V three-phase drawing 20 A per phase, PF 0.9. P = 1.73 ร 400 ร 20 ร 0.9 = 12,456 W โ 12.5 kW
Example 2: You have a 30 kW motor on 400 V, PF 0.85. What current? I = P / (โ3 ร V ร PF) = 30,000 / (1.73 ร 400 ร 0.85) โ 51 A per phase
Balanced vs unbalanced loads
In a balanced system, all three phases have the same current. Power is smooth and you can use the simple formula.
In an unbalanced system (common in buildings where single-phase loads are split unevenly across phases), one phase carries more than others. This causes:
- Neutral current (even though it should be zero)
- Harmonic distortion
- Heating in the neutral wire
- Inefficiency
Most commercial buildings are reasonably balanced because they have many small loads spread across phases.
Energy from three-phase
Energy (kWh) = Power (kW) ร Time (hours), same as single-phase.
A 10 kW three-phase motor running 8 hours uses 80 kWh.